- 1. Outline
VSM-12 series permanent magnet-type indoor high voltage vacuum circuit breaker is a three-phase AC 50Hz, rated voltage of 12kV indoor switch equipment. Installed with permanent magnetic mechanism of our company own research and development for industrial and mining enterprises, power generation and substation facilities as electrical control and protection purposes. The product with high reliability and long life characteristics, especially apply to places with serious conditions, such as frequent operation, repeated short-circuit breaking current.
- 2. Environmental Conditions
◆ Ambient temperature: -25℃~+40℃;
◆ Altitude: ≤1000m, plateau type ≤3000m;
◆ Relative humidity: daily average ≤95%, monthly average ≤90%, saturated vapor pressure daily
average ≤2.2×10 MPa, monthly average ≤1.8×10MPa. When temperature drops rapidly during
high temperature period, it may occur condensation.
◆ Earthquake intensity: ≤8 level;
◆ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense
vibration.
3. Type Description
4. Main Technical Parameters
◆ Vacuum circuit breaker main technical parameters
No |
Item |
Units |
Parameters |
||||
1 |
Rated voltage |
kV |
12 |
||||
2 |
Rated insulation level |
1min power frequency withstand voltage |
75 |
||||
Rated lightning impulse withstand voltage |
42 |
||||||
3 |
Rated current |
A |
630~ 1250 |
1250~3150 |
1250~4000* |
||
4 |
Rated short-circuit breaking current |
kA |
20 |
31.5 |
40 |
50 |
|
5 |
Rated short-circuit closing current(peak) |
50 |
80 |
100 |
125 |
||
6 |
Rated dynamic stability current(peak) |
50 |
80 |
100 |
125 |
||
7 |
Rated thermal stability current (RMS) |
20 |
31.5 |
40 |
50 |
||
8 |
Rated short-circuit breaking current breaking number |
Times |
30 |
30 |
20 |
20 |
|
9 |
Rated thermal stability time |
S |
4 |
||||
10 |
Rated operating sequence |
|
O-0.3s-CO-180s-CO |
||||
11 |
Mechanical life |
Times |
≥30000 |
||||
12 |
Mechanical life of permanent magnetic mechanism and transmission part |
Times |
≥100000 |
||||
13 |
Rated single capacitor bank breaking current |
A |
630~1250 |
||||
14 |
Rated back-to-back capacitor breaking current |
400 |
|||||
15 |
Rated out of step breaking current |
kA |
12.6 16 |
*When rated current >3150A, there should be ventilation measures.
**There are differences due to different vacuum interrupters.
◆ Mechanical properties parameters after adjustment
No |
Item |
Units |
Parameters |
1 |
Clearance distance between open contacts |
mm |
11±1* |
2 |
Contact travel |
3.5±0.5 |
|
3 |
Three phase opening synchronism |
ms |
≤2 |
4 |
Closing contact bounce time |
≤2 ≤3(40kA) |
|
5 |
Inter-phase center distance |
mm |
210, 275 |
6 |
Closing contact pressure |
N |
20kA 31.5kA 40kA 2000±200 3100±200 4500±300 |
7 |
Main conductive circuit resistance |
μΩ |
60 45 30 |
8 |
Average opening speed |
m/s |
1.1±0.2 |
9 |
Average closing speed |
0.7±0.2 0.8±0.2 |
|
10 |
Opening time |
ms |
30~60 |
11 |
Closing time |
50~100 |
|
12 |
Dynamic and fixed contact cumulative allowed wear thickness |
mm |
3 |
There are differences due to different vacuum interrupters.
◆ Permanent magnetic mechanism technical parameters
Name |
Voltage |
Item |
Unit |
I |
II |
III |
||
20kA |
25kA |
31.5kA |
40kA |
50kA |
||||
Closing coil |
DC220V |
working current (peak) |
A |
52 |
88 |
|||
Resistance |
Ω |
4.2±0.18 |
2.5±0.18 |
|||||
Opening coil |
DC220V |
working current (peak) |
A |
2 |
3.5 |
|||
Resistance |
Ω |
120±15 |
600±0.5 |
|||||
Closing coil |
AC220V |
Input current |
A |
≤2 |
|
|||
Opening coil |
AC220V |
working current (peak) |
A |
2 |
3.5 |
|||
Resistance |
Ω |
120±15 |
60±5 |
|||||
Note: if have any special requirements of power supply, please specify when ordering.
5. General Structure Drawing (unit: mm)
◆ Withdrawable type (normal pole) (cabinet width 800 or 1000mm)
Inter-phase distance 210mm (275mm)
Rated current (A) |
630 |
1250 |
1600 |
Rated short-circuit breaking current (kA) |
20, 25, 31.5 |
20, 25, 31.5, 40 |
31.5, 40 |
Matched fixed contact size (mm) |
Φ35 |
Φ49 |
Φ55 |
◆ Withdrawable type (normal pole) (cabinet width 1000mm)
Inter-phase distance 275mm
Rated current (A) |
1600 |
2000 |
2500 |
3150 |
4000* |
Rated short-circuit breaking current (kA) |
31.5 |
40 |
40, 50 |
||
Matched fixed contact size (mm) |
Φ79 |
Φ109 |
*If rated current >3150A, need forced air cooling.
◆ Fixed type (normal pole)
Inter-phase distance 210mm (275mm)
Rated current (A) |
630 |
1250 |
1600 |
Rated short-circuit breaking current (kA) |
20, 25, 31.5 |
20, 25, 31.5, 40 |
31.5, 40 |
◆ Fixed Type (normal pole)
Inter-phase distance 275mm
Rated current (A) |
1600 |
2000 |
2500 |
3150 |
4000* |
Rated short-circuit breaking current (kA) |
31.5 |
40 |
40, 50 |
*If rated current >3150A, need forced air cooling.
◆ Withdrawable type (embedded pole) (cabinet width 800 or 1000mm)
Inter-phase distance 210mm (275mm)
Rated current (A) |
630 |
1250 |
1600 |
Rated short-circuit breaking current (kA) |
20, 25, 31.5 |
20, 25, 31.5, 40 |
31.5, 40 |
Matched fixed contact size (mm) |
Φ35 |
Φ49 |
Φ55 |
◆ Withdrawable type (embedded pole) (cabinet width 1000mm)
Inter-phase distance 275mm
Rated current (A) |
1600 |
2000 |
2500 |
3150 |
4000* |
Rated short-circuit breaking current (kA) |
31.5 |
40 |
40, 50 |
||
to match fixed contact size (mm) |
Φ79 |
Φ109 |
*If rated current >3150A, need forced air cooling.
◆ Fixed type (embedded pole)
Inter-phase distance 210mm (275mm)
Rated current (A) |
630 |
1250 |
1600 |
Rated short-circuit breaking current (kA) |
20, 25, 31.5 |
20, 25, 31.5, 40 |
31.5, 40 |
◆ Fixed type (embedded pole)
Inter-phase distance 275mm
Rated current (A) |
1600 |
2000 |
2500 |
3150 |
4000* |
Rated short-circuit breaking current (kA) |
31.5 |
40 |
40, 50 |
*If rated current >3150A, need forced air cooling.