VS1-12 indoor HV vacuum circuit breaker is a 3-phase AC 50Hz 12kV indoor switch equipment.
♦ Installation way: withdrawable type, fixed type, side mounted type;
♦ Operating mechanism: spring ope rating mechanism, permanent magnetic operating mechanism;
♦ Pole type: assembled pole, embedded pole;
♦ Application: switchgear KYN28-12, XGN-12.
♦ Secondary plug: 58pins, 64pins.
Product Standards
♦ IEC62271-100 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers
♦ GB1984 High Voltage AC Circuit-breakers
♦ GB/T11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
♦ JB/T 3855 High Voltage AC Vacuum Circuit-breakers
♦ DL/T402 Specification of High-voltage AC Circuit-breakers
Environmental Conditions
♦ Ambient temperature: -15°C~+40°C;
♦ Altitude: <1000m;
♦ Relative humidity: daily average <95%, monthly average <90%;
♦ Earthquake intensity: <8 level;
♦ Places without fire, explosion hazard, serious filthy, chemical corrosion, as well as intense vibration.
Main Technical Parameters
No |
Item |
Unit |
Value |
1 | Rated voltage | kV |
12 |
2 | 1 min power frequency withstand voltage |
42 |
|
3 | Rated lightning impulse withstand voltage |
75 |
|
4 | Rated frequency | Hz |
50 |
5 | Rated current | A |
630, 1250, 1600, 2000, 2500, 3150, 4000 |
6 | Rated short circuit breaking current | kA |
20, 25, 31.5, 40 |
7 | Rated short time withstand current |
20, 25, 31.5, 40 |
|
8 | Rated short circuit duration | s |
4 |
9 | Rated peak value withstand current |
kA |
50, 63, 80, 100 |
10 | Rated short circuit making current |
50, 63, 80, 100 |
|
11 | Secondary circuit power frequency withstand voltage (1min) | V |
2000 |
12 | Rated single / back-to-back capacitor bank breaking current | A |
630/400 (800/400 for 40kA and 50kA) |
No |
Item |
Unit |
Value |
13 |
Rated capacitor bank closing inrush current | A |
12.5 |
14 |
Opening time (rated voltage) |
ms |
20-50 |
15 |
Closing time (rated voltage) |
ms |
35-70 |
16 |
Mechanical life |
Times |
10000 |
17 |
Rated current breaking number |
Times |
10000 |
18 |
Rated short circuit current breaking number |
Times |
50 (30 for 40kA; 20 for 50kA) |
19 |
Moving and fixed contacts cumulative allowed wear thickness | mm |
3 |
20 | Rated closing operating voltage | V |
AC/DC110/220 |
21 | Rated opening operating voltage | ||
22 | Rated voltage of energy storage motor |
W |
70 (80 ror 40kA and 50kA) |
23 | Rated power of energy storage motor | ||
24 | Energy storage time | s |
<10 |
25 | Clearance between open contacts | mm |
11±1 |
26 | Over travel | mm |
3.5±0.5 |
27 | Contact closing bounce time | ms |
≤2 (≤3 for 40kA and 50kA) |
28 | Three phase opening and closing asynchronism | ms |
≤2 |
29 | Average opening speed |
m/s |
0.9-1.2 |
30 | Average closing speed |
m/s |
0.5-0.8 |
31 | Main conductive circuit resistance | μΩ |
≤60 (630A) ≤50(1250A) ≤35(1600-2000A) ≤25(above 2500A) |
32 | Closing contact pressure of the contacts | N |
2000±200 (20kA) 2400±200 (25kA) 3100±200 (31.5kA) 4250±250 (40kA) 6500±500 (50kA) |
33 | Rated operating sequence |
O-0.3s-CO-180s-CO O-180s-CO-180s-CO (50kA) |
Note: when current is 4000A or 5000A, need forced air cooling.
General Structure Drawing and Installation Size (unit: mm)
♦ Draw out type
Cabinet width |
Rated current (A) |
Rated short circuit breaking current (kA) |
P | H |
A |
B |
C |
D |
E | F |
G |
J |
K |
L |
M |
N |
R |
S |
T |
650 | 630 |
20 〜31.5 |
150 | 275 | 490 | 502 | 492 |
500 |
433 | 626 |
035 |
280 | 598 | 76 | 78 | 637 | 508 | 202 | 40 |
650 | 1250 |
20 〜31.5 |
150 | 275 | 490 | 502 | 492 |
500 |
433 | 626 |
049 |
280 | 598 | 76 | 78 | 637 | 508 | 202 | 40 |
800 | 630 |
20 〜31.5 |
210 | 275 | 638 | 652 | 640 |
650 |
433 | 626 |
035 |
280 | 598 | 76 | 78 | 637 | 508 | 277 | 40 |
800 | 1250 |
20-40 |
210 | 275 | 638 | 652 | 640 |
650 |
433 | 626 |
049 |
280 | 598 | 76 | 78 | 637 | 508 | 277 | 40 |
800 | 1600 |
31.5〜40 |
210 | 275 | 638 | 652 | 640 |
650 |
433 | 626 | 055 | 280 | 598 | 76 | 78 | 637 | 508 | 277 | 40 |
1000 | 630 |
20 〜31.5 |
275 | 275 | 838 | 852 | 838 |
850 |
433 | 626 |
035 |
280 | 598 | 76 | 78 | 637 | 508 | 377 | 40 |
1000 | 1250 |
20 〜40 |
275 | 275 | 838 | 852 | 838 |
850 |
433 | 626 |
049 |
280 | 598 | 76 | 78 | 637 | 508 | 377 | 40 |
1000 | 1600 |
31.5-40 |
275 | 275 | 838 | 852 | 838 |
850 |
433 | 626 |
055 |
280 | 598 | 76 | 78 | 637 | 508 | 377 | 40 |
1000 | 1600-2000 |
31.5 〜40 |
275 | 310 | 838 | 852 | 838 |
850 |
361 | 680 |
079 |
295 | 586 | 77 | 88 | 698 | 536 | 377 |
0 |
1000 | 2500〜4000 |
31.5 〜40 |
275 | 310 | 838 | 852 | 838 |
850 |
361 | 680 |
0109 |
295 | 586 | 77 | 88 | 698 | 536 | 377 |
0 |
♦ Fixed type
Cabinet width |
Ra»a current (A) |
P |
H |
A |
C |
E |
G1 |
J |
K |
L |
650 |
630-1600 |
150 |
275 |
385 |
440 |
580 |
I |
237 |
455 |
395 |
800 |
630-1600 |
210 |
275 |
520 |
588 |
580 |
II |
237 |
455 |
410 |
1000 |
630~1600 |
275 |
275 |
720 |
770 |
580 |
II |
237 |
455 |
410 |
1000 |
1600~4000 |
275 |
310 |
720 |
770 |
632 |
III |
252 |
465 |
440 |
♦ Side mounted type