NVS1-24 Series Indoor High Voltage Vacuum Circuit Breaker

Short Description:


Product Detail

Product Tags

Summary

Our new products, NVS1-24 series indoor high-voltage vacuum circuit breakers are used for switchgears in 24kV power system, as a control and protection unit of electrical equipments in industrial and mining enterprises, power plants and substations. Due to the special advantages of the vacuum circuit breaker, it is especially suitable for frequent operations requiring rated working current, or places where the short-circuit current is broken multiple times. The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body. The two are a front and back structure, which is with reliable interlocking function. The circuit breaker can be used as a fixed installation unit. It can also be equipped with a chassis truck into a hand cart unit.

 

Product standards

GB/T1984-2014 High voltage AC Circuit Breaker

JB/T3855-2008 3.6-40.5kV indoor AC High voltage vacuum circuit breaker

DL/T403-2000 12kV-40.5kV high voltage vacuum circuit breaker ordering technical conditions

IEC62271-100:2008 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers

 

Environmental Conditions

Ambient temperature: -15 C ~+40C

O Ambient humidity: Daily average relative humidity < 95%

Daily average vapour pressure < 2.2X10MPaMonthly average relative humidity < 90%Monthly average vapour pressure < 1.8×10%MPa;

O Altitude ≤ 1000m;

O Earthquake intensity < grade 8:

O Installation spot: The spot should have no water, explosion danger, seriouspollution, chemical corrosion and exquisite shake.

 

Main Technical Parameters

Item

Unit

Data

Rated voltage

kV

24

Rated frequency

Hz

50

Rated 1 min power frequency withstand voltage (phase to phase, to earth, fracture)

kV

65

Rated lightning impulse withstand voltage (phase to phase, to earth, fracture)

kV

125

Rated operation sequence

 

O-t-CO-t’-CO

 

 

Item

Unit

NVS1-24

Rated current

A

630

1250

1250

1600

2000

2500

1250

1600

2000

2500

3150

Rated short circuit breaking current

kA

20 / 25

31.5

40

Rated short circuit making current (peak)

kA

50 / 63

80

100

Rated duration of short circuit

s

4

4

4

Rated short circuit breaking times

time

50

50

30

Mechanical life

time

20000

20000

20000

Note:

20/25/31.5kA, t=0.3s   t’=180s

40/50kA, t=180s, t’=180s

4000A VCB need forced air cooling

 

Item

Unit

Data

Clearance between open contacts

mm

13±1

Overtravel

3.5±0.5

Three phase opening and closing asynchronism

ms

≤2

Contact closing bounce time

ms

≤ 3 (50kA)

Contact pressure of closing contacts

N

20kA

25 kA

31.5 kA

40 kA

50 kA

2000±200

2400±200

3100±200

4250±250

5500±300

Average opening speed

m/s

1.1~1.6

Average closing speed

0.6~1.0

 

General Structure Drawing and Installation Size (unit: mm)

1NVS1 dimension4 1NVS1 dimension5 1NVS1 dimension6