KYN61-40.5 Metal-Claded Withdrawable Type AC Metal-Enclosed Switchgear

Short Description:


Product Detail

Product Tags

General
KYN61-40.5 type metal-claded withdrawable type AC metal-enclosed switchgear (hereinafter referred to as "switchgear") is mainly characterized by the use of ZN85-40.5 fully insulated vacuum circuit breakers and spring operating mechanisms in the cabinet, and the cabinet body is assembled by plastic coated steel, which improves the matching precision of the VCB and the cabinet. The VCB is easy to push and pull out and has strong interchangeability with beautiful appearance, complete solutions, safe and reliable use.
This product is used in 35kV three-phase AC 50Hz power system. It is used for receiving and distributing electric energy in power plants, substations and power distribution rooms of industrial and mining enterprises. It has control, protection and monitoring functions. This product complies with standards: GB3906 "Alternating-current metal-enclosed switchgear and controlgear for rated voltage above 3.6kV and up to and including 40.5kV", GB/T11022 "Common specifications for high-voltage switchgear and controlgear standards", DL/T404 "Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6kV and up to and including 40.5kV", IEC60298 "A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52kV".

Normal Use Conditions
● Ambient air temperature: -15℃~+40℃.
● Humidity conditions:
Daily average relative humidity: ≤95%, daily average water vapor pressure ≤2.2kPa.
The monthly average relative humidity is 90%, and the monthly average water vapor pressure is 1.8kPa.
● Altitude: ≤4000m.
● Earthquake intensity: ≤8 degrees.
● The surrounding air should not be contaminated by corrosive or combustible gas, water vapor, etc.
● Places without frequent severe vibration.

Type Description

1

Main Technical Parameters

Item

Unit

Value

Rated voltage

kV

40.5

Rated current Rated current of main bus

A

630, 1250, 1600

Rated current of equipped circuit breaker

A

630, 1250, 1600

Insulation level 1min power frequency withstand voltage:phase-to-phase, phase-to-earth/across open contacts

kV

95/110

Lightning impulse withstand voltage (peak):phase-to-phase, phase-to-earth,/across open contacts

kV

185/215

Power frequency withstand voltage of auxiliary circuit and control circuit

V/1 min

2000

Rated frequency

Hz

50

Rated short circuit breaking current

kA

20, 25, 31.5

Rated short time withstand current/rated short circuit duration

kA/4s

20, 25, 31.5

Rated peak withstand current

kA

50, 63, 80

Rated short circuit making current

kA

50, 63, 80

Rated voltage of control circuit

V

DC110/220, AC110/220

Protection degree Switchgear enclosure  

IP4X

Compartment (when the doors are opened)  

IP2X

Main Technical Parameters

Technical Parameters of ZN85-40.5 Type Circuit Breaker with Spring Operating Mechanism(Integrated)

Item

Unit

Value

Rated voltage

kV

40.5

Rated current

A

630, 1250, 1600

Insulation level 1min power frequency withstand voltage:phase-to-phase, phase-to-earth/across open contacts

kV

95/110

Lightning impulse withstand voltage (peak):phase-to-phase, phase-to-earth,/across open contacts

kV

185/215

Power frequency withstand voltage of auxiliary circuit and control circuit

V/1 min

2000

Rated frequency

Hz

50

Rated short circuit breaking current

kA

20, 25, 31.5

Rated short circuit making current

kA

50, 63, 80

Rated peak withstand current

kA

50, 63, 80

Rated short time withstand current/rated short circuit duration

kA/4s

20, 25, 31.5

Mechanical life

times

1000

Closing time

ms

50~100

Opening time

ms

35~60

Rated operating sequence  

O-0.3s-CO-180s-CO

Structure
This product is divided into two parts: cabinet and VCB. The cabinet is made of bent steel plate and assembled with bolts after spraying. According to functional characteristics, it can be divided into four parts: small bus room, relay instrument room, VCB room, cable room and bus room, each part is separated by a grounded metal partition. The protection degree of the switchgear enclosure is IP4X; when the VCB room door is opened, the protection degree is IP2X.

The switchgear has main circuit schemes such as cable inlet and outlet, overhead inlet and outlet, bus connection, disconnection, voltage transformer, and lightning arrester. The busbar adopts composite insulation, and the inter-phase and connectors are equipped with insulating sleeves made of flame-retardant materials. The adjacent cabinets of the main busbar are separated by busbar sleeves, which can effectively prevent the accident from spreading and play an auxiliary support role for the main busbar. The cable room is equipped with earth switch, overvoltage protection device, etc.

There is a metal safety shutter in front of the contact box. The upper and lower safety shutter are automatically opened when the VCB moves from the disconnecting/test position to the working position, and automatically closed when the VCB moves in the opposite direction, effectively disconnecting from the high voltage. The interlocking between the main switch, VCB, earth switch and cabinet door adopts mandatory mechanical interlocking method to meet the "five prevention" functional requirements.

The circuit breaker adopts a screw rod drive propulsion mechanism and an overrunning clutch. The screw rod nut feed mechanism can be easily operated to move the VCB between the test position and the working position. With the help of the self-locking property of the screw rod nut, the VCB can be reliably locked in the working position to prevent the VCB from accident caused by fleeing due to electric power. The overrunning clutch works when the VCB moves back to the test position and when it reaches the working position. It makes the operating shaft and the screw shaft automatically disengage and idle, which can prevent misoperation and damage the feed mechanism. Other VCBs use lever feed mechanism. The test work position is locked by positioning pins.
The overall dimensions of the cabinet are: W×D ×H (mm): 1400×2800×2600

1

Main Circuit Scheme Diagrams

Primary scheme NO.

1

2

3

4

5

Main circuit scheme diagram

 1  2  3  4  5
Main circuit components       Vacuum circuit breaker ZN85-40.5 1

1

1

1

1

Current transformer LZZBJ9-35  

1—3

1—3

4—6

 
Voltage transformer JDZ9-35          
Arrester HY5WZ2

0 or 3 optional

Earth switch JN24-40.5

0-1 optional

Charged display

0-1 optional

Fuse XRNP-35          
Power transformer SC9-35          