FN7-24 INDOOR HV LOAD BREAK SWITCH

Short Description:


Product Detail

Product Tags

Outline

FN7-24(DR) indoor HV load break switch applies to electric system with 24kV rated voltage and three-phase AC 50/60Hz, for connecting and breaking load current and short circuit current.

Use Conditions

A.  Altitude: ≤1000m.

B. Ambient temperature: -25℃~+40℃.

C. Relative humidity: daily average ≤95%, monthly average ≤90%.

D. No frequent serious vibration.

Main Parameters

NO.

Items

Unit

Value

1

rated voltage

kV

24

2

rated frequency

Hz

50

3

rated current

A

400, 630, 1250

4

rated active load breaking current

A

400, 630, 1250

5

Rated closed loop breaking current

A

400, 630, 1250

6

5% rated active load breaking current

A

20, 31.5, 62.5

7

rated cable charging breaking current

A

10

8

1min power frequency withstand voltage: phase-to-phase, phase to earth/ fracture

kV

50/60

9

lightning impulse withstand voltage: phase-to-phase, phase to earth/ disconnecting fracture

kV

125/145

10

rated short time withstand current (thermal stability)

kA

16, 20, 25

11

rated short circuit duration

s

1

12

rated peak withstand current

kA

40, 50, 63

13

rated short circuit making current

kA

40, 50, 63

14

mechanical life

 times

2000