Service condlton |
Type |
MOA Rated voltage kV |
System nominal vohag® kV |
Continaus operatlori voitag« kV |
DCMInUlmA reference vottage kY> |
Rssldual voltag^KV)^ |
Squarewave current br|Mte wTOistand A |
High currant Impulse kA |
||
Stoep orrent imputse |
Ufifttnlno ctmom hpdse |
Swlichlng cunwit impulse |
||||||||
Substation |
YH5WZ-3.8/13.5 |
3.8 |
3 |
3.2 | 7.2 |
14.5 |
13-5 |
11.5 |
200 |
65 |
YH5WZ-7.6/27 |
7.6 |
9 |
4.0 |
IM |
31 |
27 |
23 |
|||
YH5WZ-KM27 | 10 |
6 |
a.o |
14j4 |
31 |
27 |
23 |
|||
YH5WZ-17/45 | 17 |
10 |
13.6 | 24 |
51.8 |
45 |
38.3 |
|||
YHSWZ-42/134 |
42 |
35 |
234 | 73 |
154 |
134 |
114 |
400 |
100 |
|
YH5WZ-51/134 | 51 | 40.8 | 73 |
154 |
134 |
114 |
||||
YH5WZ-52.7/134 |
52.7 |
42.2 | 73 |
154 |
134 |
114 |
||||
YH5WZ-54/134 |
54 |
43.2 | 73 | 154 |
134 |
114 |
||||
YH5WZ-e4^21 |
84 |
66 |
57.2 | 121 |
254 |
221 |
188 |
600 |
100 |
|
YH5WZ-«M22+ |
90 |
72.5 | 130 |
26B |
224 |
190 |
||||
YH5WZ-94/224 |
94 |
75.5 | 134 |
270 |
234 |
198 |
||||
YH5WZ-96Z25O |
96 |
110 |
75 |
140 |
207 |
250 |
212 |
800 |
100 |
|
YH5WZ-10Q/260 | 100 |
78 |
14S |
289 |
260 |
221 |
||||
YH6WZ-102/280 | 102 |
80 |
148 |
306 |
286 |
226 |
||||
YH6WZ-108C81 | 108 |
84 |
167 |
323 |
281 |
239 |
||||
YH6WZ-11BQO2 |
116 |
83.2 | 168 |
347 |
302 |
256 |
||||
Substation
(Z) |
YH5WZ-51/134 |
51 |
35 |
40.8 | 73 |
154 |
134 |
114 |
400 |
100 |
YH5WZ-52.7/134 | 52.7 | 42.2 | 73 |
154 |
134 |
114 |
||||
YH5WZ-72/184 |
72 |
66 |
57 |
105 |
211 |
1B4 |
165 |
800 |
100 |
|
YHSWZ-75^23 |
75 |
60 |
127 |
256 |
223 |
190 | ||||
YH5WZ-75423O |
75 |
SO |
127 |
256 |
230 |
196 | ||||
YHSWZ-75/250 |
75 |
60 |
127 |
288 |
250 |
213 |
||||
YH5WZ84/245 |
M |
572 | 122 |
245 |
215 |
181 |
||||
YH5WZ-90/235 |
90 |
72.5 | 130 |
264 |
235 |
201 |
||||
YH5WZ-96/250 |
96 |
110 |
75 | 140 |
280 |
250 |
212 |
800 |
100 |
|
YH5WZ-100/260 | 100 | 78 | 145 |
291 |
260 |
221 |
||||
YH5WZ-1Q2/266 | 102 | 79.6 | 146 |
2S7 |
266 |
226 |
||||
YH5WZ-1CO281 | 108 | 04 | 157 |
315 |
281 |
238 |
||||
YH5WZ-116/302 | 116 | 8d | 168 |
338 |
302 |
257 |
||||
YH5WZ-120/300 | 120 | 06 | 174 |
335 |
300 |
270 |
||||
YH5WZ・126/328 | 126 | 95.8 | 183 |
307 |
328 |
27S | ||||
YH6WZ-160/400 | 150 | 115 | 230 |
444 |
400 |
352 |
Technical Parameters Of Transmission Line Moa
Tnansmission MOA type |
System vottage kVr.m.i |
Cont.Dpsr. voltafle for body kVr.m.8 |
Refer.voltage at 1 mA d.c. UlmAdx. kV |
Max.re fiidual voftsgeat limning impulse kV crest |
2msroctancular current discharge capacity A |
4/10 u a Impulse dsctarge capacity kA |
Heignt mm |
Gap distance mm |
NO.of flg |
YH10WX-18/57TL |
10 |
15 |
285 |
57 |
150 |
65 |
300 |
/ |
/ |
YH10WX-54/142TL |
35 |
43.2 |
77 |
142 |
400 |
100 |
700 |
|
S29 |
YH10WX-57H701L |
35 |
45 |
85 |
170 |
400 |
100 |
700 |
/ |
929 |
YH10WX-96/250TL |
66 |
75 |
140 |
250 |
400 |
100 |
1270 |
/ |
8BS2 |
YH10WX-10a/281TL |
110 |
84 |
157 |
287 |
4QQ |
100 |
1270 |
/ |
■32 |
YH10WX-114/2S7TL |
110 |
SQ |
105 |
287 |
400 |
100 |
1270 |
/ |
B32 |
YH10WX-120/334TL |
110 |
93 |
180 |
334 |
400 |
100 |
1270 |
/ |
»32 |
YH5CX-11/27 |
10 |
9 |
伯f |
27 |
150 |
65 |
207 |
16.5 |
■34 |
YH1QCX-42/120K |
35 |
33.6 |
60 |
120 |
4« |
100 |
8S0 |
120±20 |
圖28 |
YH10CX-42/120 |
35 |
33.6 |
60 |
120 |
400 |
100 |
940 |
120±20 |
■30 |
YH10CX-69/198K |
86 |
55.2 |
100 |
188 |
400 |
100 |
/ |
390*50 |
/ |
YH10CX-69/198 |
66 |
55.2 |
100 |
198 |
400 |
100 |
/ |
390±60 |
/ |
YH10CX-90/260 |
110 |
72 |
130 |
260 |
400 |
100 |
1S10 |
460=20 |
■33 |
YH10GX-90/260K |
110 |
72 |
130 |
260 |
400 |
100 |
1510 |
450±50 |
S31 |
YH1OCX-96/280 |
110 |
76.8 |
140 |
280 |
400 |
100 |
15。 |
460×50 |
8B33 |
YH10CX-180/520 |
110 |
76.8 |
140 |
280 |
400 |
100 |
1510 |
450±50 |
931 |
YH1 OCX-180/520K |
220 |
144 |
280 |
620 |
600 |
100 |
3100 |
960±20 |
B36 |
YH100(-180ffi20K |
220 |
144 |
260 |
520 |
600 |
100 |
2700 |
B50±20 |
■35 |
YH1 OCX-192/560 |
220 |
153.6 |
280 |
560 |
600 |
100 |
3100 |
960=20 |
S36 |
YH10GX-1S2/560K |
220 |
153.6 |
280 |
560 |
600 |
100 |
2700 |
860 土 SO |