OEM Customized China Manual Knife Load Break Switch Outdoor

Short Description:


Product Detail

Product Tags

Our company sticks into the basic principle of “Quality is definitely the life of the business, and status may be the soul of it” for OEM Customized China Manual Knife Load Break Switch Outdoor, Welcome all nice customers communicate details of products and solutions and ideas with us!!
Our company sticks into the basic principle of “Quality is definitely the life of the business, and status may be the soul of it” for China Switch Disconnector, Isolate Switch Disconnector, We have more than 8 years of experience in this industry and have a good reputation in this field. Our products have won praise from customers worldwide. Our aim is to help customers realize their goals. We are making great efforts to achieve this win-win situation and sincerely welcome you to join us.

PGS-630A pole mounted load break switch is used for breaking rated voltage 12/24/40.5kV, rated current 630A, 50/60Hz power distribution system, closing load current and over load current of power system, it could separate automatically track sections of power distribution which faults occur. The switch is matched with electronic controller which is with the latest technology. The switch has manual, motor, remote operation modes. The electronic controller would be installed inside the stainless steel box, so it could be used in various climate conditions. Besides that, the wire/wireless modem installed inside control box could achieve remote monitoring and controlling. It’s easy and convenient for installation the switch on pole, and that could reduce the execution cost.

Environmental Conditions

♦ Air temperature: -40℃~+50℃;

♦ Relative humidity: 110%

♦ Altitude ≤3000m.

♦ Wind pressure ≤700pa (equivalent to wind speed 34m/s).

♦ Seismic intensity: 8 degree.

♦ Installation site: No fire disaster, explosion danger, chemical corrosion and frequent strenuous vibration places).

♦ Pollution grade: Ⅲ class, Ⅳclass.

Type descriptions

wef

 MPP types

trh

♦ Porcelain bushing-molded cable outlet

htr (1)

♦ Rubber split bushing-molded cable outlet

htr (2)

♦ Integrative rubber bushing-wiring terminal outlet

htr (3)

♦ with surge arrestor

♦ Porcelain bushing-wiring terminal outlet

Technical Parameter

Products Type PGS-12

PGS-24

PGS-40.5
Basic Ratings
Maximum system voltage 15KV

25.8KV

40.5KV
Rated continuous current 630A 630A 630A
Rated frequency 50/60Hz

50/60Hz

50/60Hz
Short time withstand current 20KA/4s

25KA/1s

20KA/1s
Making and Breaking Capacity
Mainly active load current 630A 630A 630A
Number of load-break operations 400times

400times

400times
Short-circuit making current (peak) 50KA 50KA 50KA
Number of making operations 5 times

5 times

5 times
Cable charging current 25A 25A 25A
Line charging current 1.5A 1.5A 2A

 

Closed loop circuit current 630A 630A 630A
Rated no-load transformer breaking current 22A 22A 22A
Power Frequency Withstand Current Test
10s(wet test),phase- phase-earth, across open contacts 45KV 50KV 70KV
1min(dry test), earth, phase to earth 50KV 60KV 95KV
1min(dry test), across open contacts 50KV 60KV 110KV
Impulse Withstand Current Test( 1.2 x 50 µs )
Phase-to-phase, phase-to-earth 85KV 150KV 195KV
Across open contacts 95KV 150KV 215KV
Other Ratings & Specifications
Internal arc test 20kA /0.1 s 20kA /0.1 s 20kA /0.1 s
Arc extinction medium SF 6 Gas SF 6 Gas SF 6 Gas
Insulation medium SF 6 Gas SF 6 Gas SF 6 Gas
Creepage distance (porcelain) 550mm 840mm 1055mm
Creepage distance (silicon) 610mm 900mm 1250mm
IP level 54 54 54
Operation Performance
Closing/opening time <1sec <1sec <1sec
Mechanical operations (guaranteed) 10000times 10000times 10000times
Operating temperature (*manual type) -25(-40)~70℃ -25(-40)~70℃ -25(-40)~70℃
Gas Pressure
Rated working pressure (kg/cm2 G, at 20°C) 0.7 1.0 1.0
Explosion-protection equipment action pressure (kg/cm2 G) 4~6 4~6 4~6
Minimum working pressure (kg/cm2 G) 0.05 0.0 0.0
Gas leakage rate (cc/ s) ≤1% ≤1% ≤1%

Overall Dimensions

jty (1)

jty (2)

Dimension(mm) InstallationDimension(mm) Packing size(mm) Creep distance ofbushing(mm)
A B C Length × Width Length×Width×high
10KV 225 435 500 500×390 1100×900×700 556
24KV 300 435 500 500×390 1300×1100×700 840
40.5KV 350 435 500 700×390 1400×1200×700 1250

With this motto in mind, we have become one of the most technologically innovative, cost-efficient, and price-competitive manufacturers for OEM Manufacturer China Rps Outdoor Pole Mounted Sf6 Load Break Switch, Any involves from you might be paid out with our greatest notice!
OEM Manufacturer China Load Break Switch, Sf6 Load Break Switch, We hope to have long-term cooperation relationships with our clients. If you are interested in any of our products, please do not hesitate to send enquiry to us/company name. We ensure that you can be totally satisfied with our best solutions!