GW5-40.5 DISCONNECT SWITCH

Short Description:

GW5-40.5 outdoor high voltage disconnect switch is used to make or break high voltage circuit in rated voltage 40.5kV, AC 50/60Hz system. It is able to open and close small capacitance and inductive current.

Product Detail

Product Tags

Item

Unit

Data

Rated voltage

kV

40.5

Rated insulation level 1min power frequency withstand voltage (to earth/fracture)

kV

95/115

  Rated lightning impulse withstand voltage (peak) (to earth/fracture)

kV

185/215

Rated frequency

Hz

50

Rated current

A

630, 1250, 1600, 2000

Rated short time withstand current

kA

20, 31.5, 40

Rated peak withstand current

kA

50, 80, 100

Rated short circuit duration (main switch/earth switch)

S

4/2

Rated terminal mechanical load Horizontal longitudinal load

N

750

  Horizontal lateral load

N

500

  Vertical force

N

750

Creepage distance

mm

1013-1256

mechanical life

times

2000

Manual operating mechanism Without earthing

 

CS17, CS17G

  Control circuit voltage

V

AC220, DC110, DC220

Motorized operating mechanism Model

 

CJ6

  Motor voltage

V

AC380

  Control circuit voltage

V

AC220, AC380, DC220

  Closing/opening time

S

6±1

 